Why does the sou device work 1. Main technical characteristics

  • Simple and reliable design
  • Small weight and dimensions
  • Relay outputs for controlling actuators
  • Easy installation and maintenance
  • Low cost

Signaling device SOU-1 designed to measure the content of carbon monoxide CO in boiler rooms and other rooms in which carbon monoxide accumulation is possible. When threshold values ​​of mass concentration are exceeded, it generates sound and light alarms and sends control signals to actuators.

The scope of application of the alarm is in boiler rooms of various capacities, closed parking lots and garages, as well as in non-explosive areas of other industrial, administrative, public and residential premises in which accumulation of carbon monoxide is possible.

Structurally, the SOU-1 signaling devices are single-block, in a plastic case. On the front panel of the alarms there is a green "ON" indicator, a red "GAS" indicator, and a yellow color"FAILURE" light, "RESET" button for disabling the actuators. Under the front panel of the alarms there is a protective cover sealed with the manufacturer’s warranty sticker, green indicators K1 and K2, buttons for calibrating the alarm, groups of terminal contacts - “23 0V, 50 Hz”, “EXTERNAL EMERGENCY”, “THRESHOLD1-CO”, “THRESHOLD2-CO” and “CONTROL”.

The operating position of the alarm is vertical; a bracket is included in the delivery set for wall mounting. It is secured with two screws located on the rear panel of the device.

Peculiarities

  • Modern design of the alarm housing;
  • The presence of “dry” relay contacts with increased load capacity, allowing you to turn on (turn off) ventilation, siren and other actuators;
  • The presence of an external “emergency” input, which allows you to connect the devices in a loop together with STG-1 and SGG-6M gas alarms or connect them to a fire or security alarm system;
  • The presence of a “test” button, which allows you to check the functionality of the device and shut-off valves without using gas mixtures;
  • Possibility of connection to the DISP dispatch panel or similar devices;
  • Connection using terminal connections;
  • The ability to independently set operating modes after turning on the device;
  • Automatic zero calibration when turned on or every 14 days.

Specifications

Options Values
CO sensor type Electrochemical
Operating mode Continuous
Working position Vertical
Maximum permissible deviation from vertical position 20°
Measuring range from 0 to 200 mg/m3
Reading range from 0 to 250 mg/m3
Default threshold values, mg/m3
Threshold 1
Threshold 2

20
100
Alarm response error, %, no more ± 25
"Dry relay contacts" AC 220V 5A
Constant 30V 2.5A
Operating temperature range, °C -10 … +50
Atmosphere pressure from 84 to 106.7 kPa
Relative humidity up to 95%
Detector power supply, V from 130 to 253 50Hz
Power, VA 5
Warm-up, min, no more 60
Alarm response speed, s, no more 45
Housing protection degree IP30
Resistance to temperature and humidity according to GOST R 52931-2008 AT 3
Climatic performance UHL category 4
Explosion protection No
Dimensions, mm 190x60x120
Weight, kg 1
Mean time between failures, h 30000
Calibration interval, years 1
Service life, years
Device
Sensor

10
3

Operating modes

Alarm type Indication State
The SOU-1 signaling device is turned on The green indicator is on Voltage is applied to the SOU-1 signaling device, the signaling device is working
Precautionary The red indicator flashes at a frequency of 0.5 - 1 Hz The CO concentration has reached the value THRESHOLD 1. The relay contacts "Threshold 1 CO" are activated
Emergency The red indicator flashes at a frequency of 5 - 6 Hz and an audible alarm The CO concentration has reached the THRESHOLD 2 value. The "CO Threshold 2" relay contacts are activated. Locking state, turns off when the CO concentration decreases and after pressing the "Reset" button
Refusal The yellow indicator is on The measuring system is faulty or the electrical sensor is faulty.
External fault Double flash of the red indicator with an interval of 5s and sound alarm Occurs when an "EMERGENCY" signal is received. The relay contacts "Threshold 1 CO" and "Threshold 2 CO" switch to a position similar to the activated warning and alarm.

dimensions

  • IR flow indicator;
  • Dispatcher console DISP (Necessary for receiving the "EMERGENCY" signal and issuing an alarm)
  • Electrochemical sensor to replace the one that has lost its resource.
  • Carbon monoxide alarm SOU-1 designed: to issue an alarm about exceeding the established values ​​of the mass concentration of carbon monoxide (carbon monoxide, CO) in the air.
    Application area gas alarm SOU-1: in boiler rooms; in the residential sector of public utilities, as well as in mines, wells, parking lots, covered garages and other facilities where the release and accumulation of carbon monoxide is possible.
    Principle of operation signaling device SOU-1- electrochemical.
    The sample collection method is diffusion.
    Alarm type - stationary.
    Technical specifications: IBYAL.413534.001TU-99
    Permission from Gosgortekhnadzor: RRS 03-2223
    State Register No.: 19068-99

    Advantages of the SOU-1 signaling device:

    The presence of “dry” contacts allowing you to turn on (turn off) ventilation, siren and other actuators
    - small dimensions and weight
    - low cost

    Main technical characteristics of the SOU-1 signaling device

    Standard threshold setting, mg/m3:
    - 1st threshold - 20
    - 2nd threshold - 100
    Relative response error, %, no more than ± 25
    Triggering of “dry” relay contacts when threshold concentrations are reached:
    - 1st threshold - one group
    - 2nd threshold - two groups
    Operating temperature range, ° C 0 - +50
    Supply voltage, V 220
    Power consumption, VA, no more than 5
    Warm-up time, min, no more than 60
    Alarm response time, s, no more than 45
    Overall dimensions, mm, no more: 220x125x90
    Weight, kg, no more: 1.2
    Device service life, years, not less: 10

    Delivery set of the SOU-1 signaling device

    Alarm device, spare parts kit, technical documentation.
    For check gas detectors SOU-1 For an additional fee, 4-liter cylinders with CO, a fine adjustment valve VTR, and an IR flow indicator are supplied.

    Designed to issue sound and light alarms when the established threshold values ​​​​of the maximum permissible concentration of carbon monoxide in the air of working and residential premises are exceeded.

    Application area:
    — in boiler rooms;
    — in the residential sector of public utilities;
    - in parking lots, covered garages and other facilities where carbon monoxide may be released and accumulated.

    Principle of operation— electrochemical.
    Sample collection method- diffusion.
    Alarm type- stationary.

    Possible system composition
    Carbon monoxide alarm SOU-1.
    Valves KEG 9720 IBYAL.685181.001 -11 (DN 65, P=0.1MPa), -12 (DN 65, P=0.4MPa), -13 (DN 80, P=0.1MPa), -14 (DN 80 , Р=0.4MPa) -220V.
    Dispatch console DISP IBYAL.465213.003.
    Combustible gas alarm SGG-6M.

    Main technical characteristics

    Characteristics Values Note
    Standard threshold setting, mg/m 31st 2nd
    20 100
    Relative operation error, %, no more± 25
    Triggering of dry relay contacts
    upon reaching threshold concentrations:
    1st threshold
    2nd threshold

    one group
    one group

    "dry" parameters
    relay contacts:
    -30 V; 2.5 A
    ˜ 220 V; 5 A
    Operating temperature range, °C-10 to +50
    Degree of protection of the alarm housingIP30
    Supply voltage, Vfrom 150 to 253frequency 50±1 Hz
    Power consumption, VA, no more5
    Alarm response time, s, no more45
    Overall dimensions, mm, no more195x60x120
    Weight, kg, no more1

    Distinctive features

    — The presence of “dry” relay contacts with increased load capacity, allowing you to turn on (off) ventilation, siren and other actuators;
    — The presence of an external “emergency” input, which allows you to connect the devices in a loop together with STG-1 and SGG-6M gas alarms or connect them to a fire or security alarm system;
    — The presence of a “test” button, which allows you to check the performance of the device and shut-off valves without the use of gas mixtures;
    — Possibility of connecting to the DISP control panel or similar devices;
    — Connection using terminal connections;
    - Possibility of independently setting operating modes after turning on the device - automatic transition to the operating mode with the opening of the network valve - "o" or turning on the alarm with the opening of the network valve after pressing the "reset" button - "c".

    TECHNICAL INFORMATION